Figure 163: Separate analogue inputs for stator (STTIPHIZ, 64S)) and rotor
(ROTIPHIZ, 64R)) protection
2. It is possible to use a mixed connection that requires only two IED voltage
channels for both ROTIPHIZ and STTIPHIZ. REX060 outputs are connected in
series. This connection is not recommended and can be used only in applications
where it is proved the possibility to use it. The use of this connection leads to
reduced performances of both ROTIPHIZ and STTIPHIZ.
Section 8 1MRK 502 071-UUS A
Impedance protection
328 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual