-3V
0
3I
0
RCA = -90°, ROA = 90°
= ang(3I
0
) – ang(V
ref
)
3I
0
cos
V
ref
en06000649_ansi.vsd
ANSI06000649 V1 EN-US
Figure 192: Characteristic for RCADir equal to -90°
When OpModeSel is set to 3I03V0Cosfi the apparent residual power component in the
direction is measured.
When OpModeSel is set to 3I0 and fi the function will operate if the residual current is
larger than the setting INDirPU and the residual current angle is within the sector
RCADir ± ROADir.
The characteristic for this OpModeSel when RCADir = 0° and ROADir = 80° is shown
in figure
193.
1MRK 502 071-UUS A Section 9
Current protection
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 391
Application manual