EasyManua.ls Logo

ABB RELION 670 SERIES REG670 - Page 48

ABB RELION 670 SERIES REG670
830 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SEMOD173276-29 v3
IEC11000201-2-en.vsd
G
U
U
GEN PDIF
87G 3Id/I
SA PTUF
81 f<
SA PTOF
81 f>
FUFSPVC
60FL
OEX PVPH
24 U/f>
UV2 PTUV
27 3U<
OV2 PTOV
59 3U>
REG 670 2.0
ZGV PDIS
21 Z<
LEX PDIS
40 <
GUP PDUP
37 P<
GOP PDOP
32 P
ROV2 PTOV
59N 3Uo>
OC4 PTOC
51/67 3I->
CC RBRF
50BF 3I> BF
NS2 PTOC
46 I2>
TR PTTR
49 Ith
PSP PPAM
78 Ucos
+ REX060, REX061
AEG PVOC
50AE U/I>
CV MMXU
Meter.
ROV2 PTOV
59N UN>
ROTI PHIZ
64R R
RE
<
STTI PHIZ
64S R
SE
<
+ REX060
ROV2 PTOV
59N 3Uo>
VT
Y
Y
D
IEC11000201 V2 EN-US
Figure 2: Generator protection application with generator differential, 100%
stator ground fault and back-up protection
Section 2 1MRK 502 071-UUS A
Application
42 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual

Table of Contents