Setting Values (Range) Description
TapChgBk
(manually reset
Alarm
Auto Block
Auto&Man Block
If the input TCINPROG of TCMYLTC or TCLYLTC (84)
function block is connected to the tap changer
mechanism, then this blocking condition will be active if
the TCINPROG input has not reset when the
tTCTimeout
timer has timed out. The output TCERRAL will be
activated depending on the actual parameter setting. In
correct operation the TCINPROG shall appear during the
VRAISE/VLOWER output pulse and disappear before the
tTCTimeout
time has elapsed.
This error condition can be reset by the input RESETERR
on TCMYLTC (84) function block, or alternatively by
changing control mode of TR1ATCC (90) or TR8ATCC
(90) function to Manual and then back to Automatic.
Table continues on next page
1MRK 502 071-UUS A Section 15
Control
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 623