Trip value rec
Sequential of
events
Event recorder
Indications
Disturbance
recorder
AxRADR
BxRBDR
Disturbance Report
Binary signals
Analog signals
DRPRDRE
ANSI09000337-2-en.vsd
ANSI09000337 V2 EN-US
Figure 313: Disturbance report functions and related function blocks
For Disturbance report function there are a number of settings which also influences
the sub-functions.
Three LED indications placed above the LCD screen makes it possible to get quick
status information about the IED.
Green LED:
Steady light In Service
Flashing light Internal failure
Dark No power supply
Yellow LED:
Steady light Triggered on binary signal N with SetLEDx = Start (or Start and
Trip)
Flashing light The IED is in test mode
Table continues on next page
Section 17 1MRK 502 071-UUS A
Monitoring
702 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual