18.8.8.2 Identification
GUID-C8113B08-3586-412C-A750-606159B1E97E v1
Function description Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
Supervison status for IEC
60870-5-103
I103SUPERV - -
18.8.8.3 Function block
GUID-69C2C974-2D64-4174-9F9A-15383C09050D v1
IEC10000293-1-en.vsd
I103SUPERV
BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL
IEC10000293 V1 EN-US
Figure 600: I103SUPERV function block
18.8.8.4 Signals
PID-3976-INPUTSIGNALS v4
Table 872: I103SUPERV Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
32_MEASI BOOLEAN 0 Information number 32, measurand supervision of I
33_MEASU BOOLEAN 0 Information number 33, measurand supervision of V
37_IBKUP BOOLEAN 0 Information number 37, I high-high back-up protection
38_VTFF BOOLEAN 0 Information number 38, fuse failure VT
46_GRWA BOOLEAN 0 Information number 46, group warning
47_GRAL BOOLEAN 0 Information number 47, group alarm
18.8.8.5 Settings
PID-3976-SETTINGS v4
Table 873: I103SUPERV Non group settings (basic)
Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
1MRK 502 066-UUS B Section 18
Station communication
1171