Name Type Description
PICKUP BOOLEAN Common pickup signal
PU_ST1 BOOLEAN Common pickup signal from step1
PU_ST1_A BOOLEAN Pickup signal from step1 phase A
PU_ST1_B BOOLEAN Pickup signal from step1 phase B
PU_ST1_C BOOLEAN Pickup signal from step1 phase C
PU_ST2 BOOLEAN Common pickup signal from step2
PU_ST2_A BOOLEAN Pickup signal from step2 phase A
PU_ST2_B BOOLEAN Pickup signal from step2 phase B
PU_ST2_C BOOLEAN Pickup signal from step2 phase C
9.2.5 Settings
PID-3535-SETTINGS v6
Table 342: OV2PTOV (59) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
OperationStep1 Disabled
Enabled
- - Enabled Enable execution of step 1
Characterist1 Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
- - Definite time Selection of time delay curve type for step
1
OpMode1 1 out of 3
2 out of 3
3 out of 3
- - 1 out of 3 Number of phases required for op (1 of 3, 2
of 3, 3 of 3) from step 1
Pickup1 1.0 - 200.0 %VB 0.1 120.0 Voltage pickup value (Definite-Time &
Inverse-Time curve) in % of VBase, step 1
t1 0.00 - 6000.00 s 0.01 5.00 Definitive time delay of step 1
t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves
for step 1
TD1 0.05 - 1.10 - 0.01 0.05 Time dial multiplier for the inverse time
delay for step 1
HystAbs1 0.0 - 50.0 %VB 0.1 0.5 Absolute hysteresis in % of VBase, step 1
OperationStep2 Disabled
Enabled
- - Enabled Enable execution of step 2
Characterist2 Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
- - Definite time Selection of time delay curve type for step
2
OpMode2 1 out of 3
2 out of 3
3 out of 3
- - 1 out of 3 Number of phases required for op (1 of 3, 2
of 3, 3 of 3) from step 2
Table continues on next page
Section 9 1MRK 502 066-UUS B
Voltage protection
614
Technical manual