14.8.5 Settings
PID-3575-SETTINGS v5
Table 557: SPC8GAPC Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
PulseMode1 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for
output 1
tPulse1 0.01 - 6000.00 s 0.01 0.10 Pulse time output 1
PulseMode2 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for
output 2
tPulse2 0.01 - 6000.00 s 0.01 0.10 Pulse time output 2
PulseMode3 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for
output 3
tPulse3 0.01 - 6000.00 s 0.01 0.10 Pulse time output 3
PulseMode4 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for
output 4
tPulse4 0.01 - 6000.00 s 0.01 0.10 Pulse time output 4
PulseMode5 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for
output 5
tPulse5 0.01 - 6000.00 s 0.01 0.10 Pulse time output 5
PulseMode6 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for
output 6
tPulse6 0.01 - 6000.00 s 0.01 0.10 Pulse time output 6
PulseMode7 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for
output 7
tPulse7 0.01 - 6000.00 s 0.01 0.10 Pulse time output 7
PulseMode8 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for
output 8
tPulse8 0.01 - 6000.00 s 0.01 0.10 Pulse time output 8
14.8.6 Operation principle
SEMOD176471-4 v6
The PSTO input selects the operator place (LOCAL, REMOTE or ALL). One of the eight outputs is
activated based on the command sent from the operator place selected. The settings
Latchedx
and
tPulsex
(where x is the respective output) will determine if the signal will be pulsed (and how
long the pulse is) or latched (steady). BLOCK will block the operation of the function – in case a
command is sent, no output will be activated.
PSTO is the universal operator place selector for all control functions. Although,
PSTO can be configured to use LOCAL or ALL operator places only, REMOTE
operator place is used in SPC8GAPC function.
Section 14 1MRK 502 066-UUS B
Control
916
Technical manual