15.7.2.2 Signals
GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1
PID-3792-INPUTSIGNALS v2
Table 648: INDCOMBSPQT Input signals
Name Type Default Description
SP_IN BOOLEAN 0 Single point indication
TIME GROUP
SIGNAL
0 Timestamp
BLOCKED BOOLEAN 0 Blocked for update
SUBST BOOLEAN 0 Substituted
INVALID BOOLEAN 0 Invalid value
TEST BOOLEAN 0 Testmode
PID-3792-OUTPUTSIGNALS v2
Table 649: INDCOMBSPQT Output signals
Name Type Description
SP_OUT BOOLEAN Single point indication
15.7.2.3 Technical data
GUID-27DF23C0-A0B2-4BB0-80B5-FC7B7F7FE448 v1
Table 650: Number of INDCOMBSPQT instances
Logic block Quantity with cycle time
3 ms 8 ms 100 ms
INDCOMBSPQT - 10 10
15.7.3 Single point input signal attributes converting function block
INDEXTSPQT
GUID-9C3D6C45-6B3A-466C-86A1-3DBCD4809B33 v1
GUID-9B700C69-4DAE-434A-BCE6-CE2D1139680A v2
The value part of the single point input signal SI_IN is copied to SI_OUT output. The time part of
single point input is copied to the TIME output. The state bits in the common part and the
indication part of the input signal are copied to the corresponding state output.
INDEXTSPQT can propagate the quality, the value and the time stamps of the signals via IEC61850.
Section 15 1MRK 502 066-UUS B
Logic
970
Technical manual