approximately calculate a secondary e.m.f. of the CT comparable with E
al
. By
comparing this with the required rated equivalent limiting secondary e.m.f. E
alreq
it is
possible to judge if the CT fulfills the requirements. The requirements according to
some other standards are specified below.
25.1.7.1
Current transformers according to IEC 61869-2, class P, PR
M11623-6 v4
A CT according to IEC 61869-2 is specified by the secondary limiting e.m.f. E
ALF
. The
value of the E
ALF
is approximately equal to the corresponding E
al
. Therefore, the CTs
according to class P and PR must have a secondary limiting e.m.f. E
ALF
that fulfills the
following:
ALF alreq
E max E
EQUATION1383 V4 EN-US (Equation 528)
25.1.7.2 Current transformers according to IEC 61869-2, class PX, PXR (and old
IEC 60044-6, class TPS and old British Standard, class X)
M11623-14 v5
CTs according to these classes are specified approximately in the same way by a rated
knee point e.m.f. E
knee
(E
k
for class PX and PXR, E
kneeBS
for class X and the limiting
secondary voltage
V
al
for TPS). The value of the E
knee
is lower than the corresponding
E
al
according to IEC 61869-2. It is not possible to give a general relation between the
E
knee
and the E
al
but normally the E
knee
is approximately 80 % of the E
al
. Therefore,
the CTs according to class PX, PXR, X and TPS must have a rated knee point e.m.f.
E
knee
that fulfills the following:
(1 )= × + - ×
Old Calculated
S TD S TD S
EQUATION1893.ANSI V1 EN-US (Equation 529)
25.1.7.3 Current transformers according to ANSI/IEEE
M11623-22 v6
Current transformers according to ANSI/IEEE are partly specified in dif
ferent ways. A
rated secondary terminal voltage
V
ANSI
is specified for a CT of class C. V
ANSI
is the
secondary terminal voltage the CT will deliver to a standard burden at 20 times rated
secondary current without exceeding 10 % ratio correction. There are a number of
standardized V
ANSI
values for example, V
ANSI
is 400 V for a C400 CT. A
corresponding rated equivalent limiting secondary e.m.f. E
alANSI
can be estimated as
follows: