RefSource: This setting is used to select the reference source between input and setting
for comparison.
Input REF: The function will take reference value from input REF
Set Value: The function will take reference value from setting SetV
alue
SetValue: This setting is used to set the reference value for comparison when setting
RefSource is selected as SetValue.
17.13.4 Setting example
GUID-13302FD6-1585-42FE-BD6D-44F231982C59 v2
For absolute comparison between inputs:
Set the EnaAbs = Absolute
Set the RefSource = Input REF
Similarly for Signed comparison between inputs
Set the EnaAbs = Signed
Set the RefSource =Input REF
For absolute comparison between input and setting
Set the EnaAbs = Absolute
Set the RefSource = Set Value
SetValue shall be set between -2000000000 to 2000000000
Similarly for signed comparison between input and setting
Set the EnaAbs = Signed
Set the RefSource = Set Value
SetValue shall be set between -2000000000 to 2000000000
1MRK 504 163-UUS A Section 17
Logic
Transformer protection RET670 2.2 ANSI 859
Application manual