Parallel line is out of service and grounded in both ends
GUID-345B36A6-B5FB-46DD-B5AE-81A1599FFC6E v1
Apply the same measures as in the case with a single set of setting parameters. This
means that an underreaching zone must not overreach the end of a protected circuit for
the single phase-to-ground faults.
Set the values of the corresponding zone (zero-sequence resistance and reactance)
equal to:
R
0E
R
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
+
è ø
ç ÷
æ ö
×=
EQUATION561 V1 EN-US (Equation 291)
X
0E
X
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
è ø
ç ÷
æ ö
×=
EQUATION562 V1 EN-US (Equation 292)
8.12.3.6 Setting the reach with respect to load
GUID-ED84BDE6-16CD-45ED-A45D-5CFB828A9040 v6
Set separately the expected fault resistance for phase-to-phase faults RFPPZx and for
the phase-to-ground faults RFPGZx for each zone. For each distance zone, set all
remaining reach setting parameters independently of each other
.
The final reach in the resistive direction for phase-to-ground fault loop measurement
automatically follows the values of the line-positive and zero-sequence resistance, and
at the end of the protected zone is equal to equation 293.
( )
1
R 2 R1 R0 RFPG
3
= × + +
ANSIEQUATION2303 V1 EN-US (Equation 293)
2X1Zx X0Zx
arctan
2 R1Zx R0Zx
loop


EQUATION2304 V2 EN-US (Equation 294)
Section 8 1MRK 504 163-UUS A
Impedance protection
388 Transformer protection RET670 2.2 ANSI