Name of OUTx Type Description Value when
activated
Value when
deactivated
OUT14 BOOLEAN Output 14 8192 0
OUT15 BOOLEAN Output 15 16384 0
OUT16 BOOLEAN Output 16 32768 0
The sum of the numbers in column “Value when activated” when all OUTx (1≤x≤16)
are active equals 65535. This is the highest integer that can be converted by the
ITBGAPC function block.
17.12 Elapsed time integrator with limit transgression and
overflow supervision TEIGAPC
17.12.1
Identification
GUID-1913E066-37D1-4689-9178-5B3C8B029815 v3
Function Description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2 device
number
Elapsed time integrator TEIGAPC - -
17.12.2 Application
GUID-B4B47167-C8DE-4496-AEF1-5F0FD1768A87 v2
The function TEIGAPC is used for user-defined logics and it can also be used for
dif
ferent purposes internally in the IED. An application example is the integration of
elapsed time during the measurement of neutral point voltage or neutral current at
earth-fault conditions.
Settable time limits for warning and alarm are provided. The time limit for overflow
indication is fixed to 999999.9 seconds.
17.12.3 Setting guidelines
GUID-2911D624-87D5-4427-BB2F-E0D1072394FA v3
The settings tAlarm and tWarning are user settable limits defined in seconds. The
achievable resolution of the settings depends on the level of the values defined.
A resolution of 10 ms can be achieved when the settings are defined within the range
1.00 second ≤ tAlarm99 999.99 seconds
1.00 second ≤ tWarning99 999.99 seconds.