EasyManua.ls Logo

ABB RELION RET670 - Setting Guidelines

ABB RELION RET670
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IEC16000038-1-en.vsdx
AP1
PhyPortB
PhyPortA
AP1
PhyPortA
PhyPortB
AP1
PhyPortA
PhyPortB
AP1
PhyPortB
PhyPortA
Device 1 Device 2
Device 3
Device 4
IEC16000038 V1 EN-US
Figure 415: High-availability Seamless Redundancy (HSR)
20.2.3 Setting guidelines
GUID-887B0AE2-0F2E-414D-96FD-7EC935C5D2D8 v1
Redundant communication is configured with the Ethernet configuration tool in
PCM600.
Redundancy: redundant communication is activated when the parameter is set to
PRP-0, PRP-1 or HSR. The settings for the next access point will be hidden and
PhyPortB will show the second port information. Redundant communication is
activated after a common write to IED is done.
PRP-1 should be used primarily, PRP-0 is intended only for use in existing PRP-
networks. PRP-1 and HSR can be combined in a mixed network.
If the access point is not taken into operation, the write option in Ethernet
Configuration Tool can be used to activate the access point.
1MRK 504 163-UUS A Section 20
Ethernet-based communication
Transformer protection RET670 2.2 ANSI 927
Application manual

Table of Contents

Related product manuals