ABB RELION RET670 - Sensitive Directional Residual Overcurrent and Power Protection SDEPSDE (67 N)

ABB RELION RET670
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AngleRCA
Forward
Area
Iop = I2
Vpol=-V2
Reverse
Area
ANSI10000031-1-en.vsd
ANSI10000031 V1 EN-US
Figure 276: Relay characteristic angle given in degree
In a transmission network a normal value of RCA is about 80°.
VPolMin: Minimum polarization (reference) voltage % of VBase.
I>Dir: Operate residual current level for directional comparison scheme. The setting is
given in % of IBase. The pickup forward or pickup reverse signals can be used in a
communication scheme. The appropriate signal must be configured to the
communication scheme block.
9.6 Sensitive directional residual overcurrent and power
protection SDEPSDE (67N)
SEMOD171436-1 v4
1MRK 504 163-UUS A Section 9
Current protection
Transformer protection RET670 2.2 ANSI 555