This means that the reach is reduced in reactive and resistive directions. If the real and
imaginary components of the constant A are equal to equation 169 and equation 170.
Re( ) 0 (2 1 0 3 ) 0 ( 0 2 1)A R R R Rf X X X= × × + + × - × + ×
EQUATION1285 V1 EN-US (Equation 169)
0 1 0 1 0 1 0
Im( ) (2 3 ) (2 )A X R R R R X X= × × + + × + × × +
EQUATION1286 V1 EN-US (Equation 170)
The real component of the KU factor is equal to equation 171.
Re
Re
Re Im
K
A X
A A
u
m
( )
= +
( )
( )
+
( )
1
0
2
2 2
EQUATION1287 V3 EN-US (Equation 171)
The imaginary component of the same factor is equal to equation 172.
( )
( )
( ) ( )
2
0
2 2
Im
Im
Re Im
m
U
A X
K
A A
×
=
+
é ù é ù
ë û ë û
EQUATION1288 V2 EN-US (Equation 172)
Ensure that the underreaching zones from both line ends will overlap a sufficient
amount (at least 10%) in the middle of the protected circuit.
8.5.2.8
Tapped line application
SEMOD154680-265 v1
1MRK 504 163-UUS A Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI 303
Application manual