EasyManua.ls Logo

ABB RELION RET670 - Distance Protection

ABB RELION RET670
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
sn R
al alreq CT L
2
pn n
f
I
S
E E I R R
I I
³ = × + +
æ ö
×
ç ÷
è ø
EQUATION1674 V1 EN-US (Equation 518)
where:
I
f
Maximum primary fundamental frequency current that passes two main CTs without passing the
power transformer (A)
25.1.6.2 Distance protection
M11619-3 v5
The current transformers must have a rated equivalent limiting secondary e.m.f. E
al
that is lar
ger than the maximum of the required rated equivalent limiting secondary
e.m.f. E
alreq
below:
sn
R
al a lreq CT L
2
pn n
k ma x
I I
S
E E R R
I I
³ = × + +
æ ö
×
ç ÷
è ø
EQUATION1675 V1 EN-US (Equation 519)
sn
R
al alre q CT L
2
pn n
kzone1
I I
S
E E R R
I I
³ = × + +
æ ö
×
ç ÷
è ø
EQUATION1676 V1 EN-US (Equation 520)
where:
I
kmax
Maximum primary fundamental frequency current for close-in forward and
reverse faults (A)
I
kzone1
Maximum primary fundamental frequency current for faults at the end of zone 1
reach (A)
I
pr
The rated primary CT current (A)
I
sr
The rated secondary CT current (A)
I
n
The nominal current of the protection IED (A)
R
ct
The secondary resistance of the CT (W)
R
L
The resistance of the secondary wire and additional load (W). In solidly
grounded
systems the loop resistance containing the phase and neutral wires
should be used for phase-to-ground faults and the resistance of the phase wire
should be used for three-phase faults.
In isolated or high impedance grounded systems the resistance of the single
secondary wire can always be used.
S
R
The burden of an IED current input channel (VA). S
R
=0.020
VA/channel for I
r
=1
A and S
R
=0.150 VA/channel for I
r
=5 A
Table continues on next page
1MRK 504 163-UUS A Section 25
Requirements
Transformer protection RET670 2.2 ANSI 989
Application manual

Table of Contents

Related product manuals