EasyManua.ls Logo

ABB RELION RET670 - Setting of Reach in Resistive Direction

ABB RELION RET670
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
0
0 1
2 1 0
m
f
Z
K
Z Z R
= -
× + +
EQUATION1426 V1 EN-US (Equation 225)
If the denominator in equation 225 is called B and Z0m is simplified to X0m, then the
real and imaginary part of the reach reduction factor for the overreaching zones can be
written as:
( )
( )
( ) ( )
2 2
0 Re
Re 0 1
Re Im
X m B
K
B B
×
= -
+
EQUATION1427 V2 EN-US (Equation 226)
( )
( )
( ) ( )
2 2
0 Im
Im 0
Re Im
X m B
K
B B
×
=
+
EQUATION1428 V2 EN-US (Equation 227)
Parallel line is out of service and grounded in both ends
GUID-AEF4E5D3-A486-4DC7-8B95-83AADE67F966 v1
Apply the same measures as in the case with a single set of setting parameters. This
means that an underreaching zone must not overreach the end of a protected circuit for
the single phase-to-
ground faults.
Set the values of the corresponding zone (zero-sequence resistance and reactance)
equal to:
R
0E
R
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
+
è ø
ç ÷
æ ö
×=
EQUATION561 V1 EN-US (Equation 228)
X
0E
X
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
è ø
ç ÷
æ ö
×=
EQUATION562 V1 EN-US (Equation 229)
8.9.3.6 Setting of reach in resistive direction
GUID-3BFE80FD-8A51-4B71-8762-73DFA73AB28B v2
Set the resistive independently for each zone.
Set separately the expected fault resistance for phase-to-phase faults RFPP and for the
phase-to-ground faults RFPG for each zone. For each distance zone, set all remaining
reach setting parameters independently of each other.
1MRK 504 163-UUS A Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI 341
Application manual

Table of Contents

Related product manuals