Check the reduction of a reach for the overreaching zones due to the effect of the zero
sequence mutual coupling. The reach is reduced for a factor:
0
0 1
2 1 0
m
f
Z
K
Z Z R
= -
× + +
EQUATION1426 V1 EN-US (Equation 180)
If the denominator in equation 180 is called B and Z0m is simplified to X0m, then the
real and imaginary part of the reach reduction factor for the overreaching zones can be
written as:
( )
( )
( ) ( )
2 2
0 Re
Re 0 1
Re Im
X m B
K
B B
×
= -
+
EQUATION1427 V2 EN-US (Equation 181)
( )
( )
( ) ( )
2 2
0 Im
Im 0
Re Im
X m B
K
B B
×
=
+
EQUATION1428 V2 EN-US (Equation 182)
Parallel line is out of service and grounded in both ends
SEMOD154704-69 v3
Apply the same measures as in the case with a single set of setting parameters. This
means that an underreaching zone must not overreach the end of a protected circuit for
the single phase-to-ground faults. Set the values of the corresponding zone (zero-
sequence resistance and reactance) equal to:
R
0E
R
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
+
è ø
ç ÷
æ ö
×=
EQUATION561 V1 EN-US (Equation 183)
X
0E
X
0
1
X
m0
2
R
0
2
X
0
2
+
--------------------------
–
è ø
ç ÷
æ ö
×=
EQUATION562 V1 EN-US (Equation 184)
8.5.3.6 Setting of reach in resistive direction
SEMOD154704-76 v1
Set the resistive reach independently for each zone, for phase-to-ground loop (RIPE)
measurement.
1MRK 504 163-UUS A Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI 309
Application manual