EasyManua.ls Logo

ABB RELION RET670 - Meshed Network Without Parallel Line

ABB RELION RET670
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MultPU: The set operate current can be changed by activation of the binary input
MULTPU
to the set factor MultPU.
9.1.3.1 Meshed network without parallel line
M12915-9 v8
The following fault calculations have to be done for three-phase, single-phase-to-
ground and two-phase-to-ground faults. With reference to Figure
256, apply a fault in
B and then calculate the current through-fault phase current I
fB
. The calculation should
be done using the minimum source impedance values for Z
A
and the maximum source
impedance values for Z
B
in order to get the maximum through fault current from A to
B.
~
~
Z
A
Z
B
Z
L
A B
IED
I
fB
Fault
ANSI09000022-1-en.vsd
ANSI09000022 V1 EN-US
Figure 256: Through fault current from A to B: I
fB
Then a fault in A has to be applied and the through fault current I
fA
has to be
calculated, Figure
257. In order to get the maximum through fault current, the
minimum value for Z
B
and the maximum value for Z
A
have to be considered.
1MRK 504 163-UUS A Section 9
Current protection
Transformer protection RET670 2.2 ANSI 515
Application manual

Table of Contents

Related product manuals