EasyManua.ls Logo

ABB RELION RET670 - Interlocking for Bus-Section Breaker A1 A2_BS (3)

ABB RELION RET670
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
If there is no second busbar B at the other side of the transformer and therefore no 489
disconnector, then the state for
489 is set to open by setting the appropriate module
inputs as follows:
489_OP = 1
489_CL = 0
15.3.5 Interlocking for bus-section breaker A1A2_BS (3)
IP14154-1 v2
15.3.5.1 Application
M15110-3 v7
The interlocking for bus-section breaker (A1A2_BS ,3) function is used for one bus-
section circuit breaker between section 1 and 2 according to figure
335. The function
can be used for different busbars, which includes a bus-section circuit breaker
.
WA1 (A1)
289
489G
189
389G
WA2 (A2)
en04000516_ansi.vsd
289G
189G
A1A2_BS
152
ANSI04000516 V1 EN-US
Figure 335: Switchyard layout A1A2_BS (3)
M15111-4 v3
The signals from other bays connected to the module A1A2_BS are described below.
15.3.5.2 Signals from all feeders
M15111-6 v4
If the busbar is divided by bus-section circuit breakers into bus-sections and both
circuit breakers are closed, the opening of the circuit breaker must be blocked if a bus-
coupler connection exists between busbars on one bus-section side and if on the other
bus-section side a busbar transfer is in progress:
1MRK 504 163-UUS A Section 15
Control
Transformer protection RET670 2.2 ANSI 733
Application manual

Table of Contents

Related product manuals