ABB RELION RET670 - Load Encroachment Characteristics

ABB RELION RET670
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
R
X
IEC08000437.vsd
IEC08000437 V1 EN-US
Figure 166: Rotation of load characteristic for a fault between two phases
This rotation may seem a bit awkward, but there is a gain in selectivity by using the
same measurement as for the quadrilateral characteristic since not all phase-to-phase
loops will be fully affected by a fault between two phases. It should also provide better
fault resistive coverage in quadrant 1. The relative loss of fault resistive coverage in
quadrant 4 should not be a problem even for applications on series compensated lines.
8.10.3 Load encroachment characteristics
GUID-DD9A62C3-A56D-411B-8303-6F7BC4C6092D v1
The phase selector must at least cover the overreaching zone 2 in order to achieve
correct phase selection for utilizing single-phase autoreclosing for faults on the entire
line. It is not necessary to cover all distance protection zones. A safety margin of at
least 10% is recommended. In order to get operation from distance zones, the phase
selection output PHSELZ or PHSELI must be connected to input PHSEL on distance
zones.
1MRK 504 163-UUS A Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI 351
Application manual