EasyManua.ls Logo

ABB RELION RET670 - Page 221

ABB RELION RET670
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
reactive voltage drop D V
L
on X
L1
line impedance leads the current by 90 degrees.
Voltage drop D
V
C
on series capacitor lags the fault current by 90 degrees. Note that
line impedance X
L1
could be divided into two parts: one between the IED point and the
capacitor and one between the capacitor and the fault position. The resulting voltage
V
M
in IED point is this way proportional to sum of voltage drops on partial
impedances between the IED point and the fault position F, as presented by
( )
M F L1 C
V I j X X= × -
EQUATION1995-ANSI V1 EN-US (Equation 57)
en06000605_ansi.vsd
~
21
XS
X
L1
IF
V
V
M
Source
Fault voltage
Pre -fault voltage
X
C
Source voltage
V
M
With bypassed
capacitor
With inserted
capacitor
F
X
ANSI06000605 V1 EN-US
Figure 92: Voltage inversion on series compensated line
en06000606_ansi.vsd
I
F
V
S
V
M
=
xV
L
xV
S
I
F
x
V
L
V
S
x
V
C
V
M
xV
S
With bypassed
capacitor
With inserted
capacitor
ANSI06000606 V1 EN-US
Figure 93: Phasor diagrams of currents and voltages for the bypassed and
inserted series capacitor during voltage inversion
It is obvious that voltage V
M
will lead the fault current I
F
as long as X
L1
> X
C
. This
situation corresponds, from the directionality point of view, to fault conditions on line
1MRK 504 163-UUS A Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI 215
Application manual

Table of Contents

Related product manuals