2
load min
Z
V
S
=
EQUATION1718 V1 EN-US (Equation 95)
Where:
V is the minimum phase-to-phase voltage in kV
S is the maximum apparent power in MVA.
The load impedance [Ω/phase] is a function of the minimum operation voltage and the
maximum load current:
min
load
ma x
Z
V
3 I
=
×
EQUATION1719 V1 EN-US (Equation 96)
Minimum voltage Vmin and maximum current Imax are related to the same operating
conditions. Minimum load impedance occurs normally under emergency conditions.
Because a safety margin is required to avoid load encroachment under
three-phase conditions and to guarantee correct healthy phase IED
operation under combined heavy three-phase load and ground faults,
consider both: phase-to-phase and phase-to-
ground fault operating
characteristics.
To avoid load encroachment for the phase-to-ground measuring elements, the set
resistive reach of any distance protection zone must be less than 80% of the minimum
load impedance.
load
RFP G 0.8 Z£ ×
EQUATION1720 V1 EN-US (Equation 97)
This equation is applicable only when the loop characteristic angle for the single
phase-to-ground faults is more than three times as large as the maximum expected
load-impedance angle. More accurate calculations are necessary according to the
equation below:
Section 8 1MRK 504 163-UUS A
Impedance protection
246 Transformer protection RET670 2.2 ANSI
Application manual