R
X
RLdFwd
RLdRev
LdAngle
LdAngle
LdAngle
LdAngle
en05000196_ansi.vsd
ANSI05000196 V1 EN-US
Figure 162: Characteristic of load encroachment function
The influence of load encroachment function on the operation characteristic is
dependent on the chosen operation mode of the FRPSPDIS (21) function. When output
signal PHSELZis selected, the characteristic for the FRPSPDIS (21) (and also zone
measurement depending on settings) can be reduced by the load encroachment
characteristic (as shown in figure
163).
1MRK 504 163-UUS A Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI 347
Application manual