EasyManua.ls Logo

ABB RELION RET670 - Page 551

ABB RELION RET670
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
51N
alt
Three phase CT
summated
Single CT
WYE/DELTA or WYE/WYE
transformer
en05000490_ansi.vsd
ANSI05000490 V1 EN-US
Figure 271: Residual overcurrent protection application on a directly grounded
transformer winding
In this case the protection has two different tasks:
Detection of ground faults on the transformer winding.
Detection of ground faults in the power system.
It can be suitable to use a residual overcurrent protection with at least two steps. Step 1
shall have a short definite time delay and a relatively high current setting, in order to
detect and clear high current ground faults in the transformer winding or in the power
system close to the transformer. Step 2 shall have a longer time delay (definite or
inverse time delay) and a lower current operation level. Step 2 shall detect and clear
transformer winding ground faults with low ground-fault current, that is, faults close to
the transformer winding neutral point. If the current setting gap between step 1 and
step 2 is large another step can be introduced with a current and time delay setting
between the two described steps.
The transformer inrush current will have a large residual current component. To
prevent unwanted function of the ground-fault overcurrent protection, the 2nd
harmonic restrain blocking should be used, at least for the sensitive step 2.
If the protected winding will not feed ground-fault (residual) current to ground faults in
the connected power system, the application is as shown in Figure
272.
1MRK 504 163-UUS A Section 9
Current protection
Transformer protection RET670 2.2 ANSI 545
Application manual

Table of Contents

Related product manuals