EasyManua.ls Logo

ABB RELION RET670 - Page 671

ABB RELION RET670
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
then exact replica of the existing relay will be achieved. The following table
summarizes all required settings for the multi-purpose function:
Setting Group1
Operation On
CurrentInput MaxPh
IBase 1000
VoltageInput MaxPh
UBase 20.50
OPerHarmRestr Off
I_2ndI_fund 20.0
BlkLevel2nd 5000
EnRestrainCurr Off
RestrCurrInput PosSeq
RestrCurrCoeff 0.00
RCADir -75
ROADir 75
LowVolt_VM 0.5
OC1
Setting Group1
Operation_OC1 On
StartCurr_OC1 30.0
CurrMult_OC1 2.0
CurveType_OC1 Programmable
tDef_OC1 0.00
k_OC1 1.00
tMin1 30
tMin_OC1 1.40
ResCrvType_OC1 Instantaneous
tResetDef_OC1 0.00
P_OC1 1.000
A_OC1 118.55
B_OC1 0.640
C_OC1 0.000
1MRK 504 163-UUS A Section 13
System protection and control
Transformer protection RET670 2.2 ANSI 665
Application manual

Table of Contents

Related product manuals