Section 6 Testing functionality
6.1 Testing disturbance report
6.1.1 Introduction
The following sub-functions are included in the disturbance report function:
Disturbance recorder
Event list
Event recorder
Trip value recorder
Indications
If the disturbance report is enabled, then its sub-functions are also set up and so it is not
possible to only disable these sub-functions. The disturbance report function is disabled
(parameter Operation = Disabled) in PCM600 or the local HMI under Main menu/
Settings/IED Settings/Monitoring/Disturbance report/DRPRDRE:1.
6.1.2 Disturbance report settings
When the IED is in test mode, the disturbance report can be made active or inactive. If the
disturbance recorder is turned on during test mode, recordings will be made. When test
mode is switched off all recordings made during the test session are cleared.
Setting OpModeTest for the control of the disturbance recorder during test mode are
located on the local HMI under Main menu/Settings/IED Settings/Monitoring/
Disturbance report/DRPRDRE:1.
6.2 Identifying the function to test in the technical reference
manual
Use the technical manual to identify function blocks, logic diagrams, input and output
signals, setting parameters and technical data.
1MRK 505 293-UUS A Section 6
Testing functionality
45
Commissioning manual

Table of Contents

Other manuals for ABB REQ650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REQ650 and is the answer not in the manual?

ABB REQ650 Specifications

General IconGeneral
BrandABB
ModelREQ650
CategoryProtection Device
LanguageEnglish

Related product manuals