EasyManua.ls Logo

ABB REQ650 - Completing the Test

ABB REQ650
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7. Instantaneously decrease the voltage in one phase to a value about 20% lower than
the measured operate value.
8. Measure the time delay for the TRIP signal, and compare it with the set value.
9. Check the inverse time delay by injecting a voltage corresponding to 0.8 ×
Vpickup<.
For example, if the inverse time curve A is selected, the trip signals
TRST1 and TRIP operate after a time corresponding to the equation:
( )
1
1
TD
t s
V
Vpickup
=
æ ö
-
ç ÷
<
è ø
ANSIEQUATION2428 V1 EN (Equation 15)
where:
t(s) Operate time in seconds
TD1 Settable time multiplier of the function for step 1
V Measured voltage
Vpickup< Set pickup voltage for step 1
For example, if the measured voltage jumps from the rated value to 0.8 times the set
pickup voltage level and time multiplier TD1 is set to 0.05 s (default value), then the
TRST1 and TRIP signals operate at a time equal to 0.250 s ± tolerance.
10. The test above can be repeated to check the inverse time characteristic at different
voltage levels.
11. Repeat the above-described steps for step
2.
Extended testing
1. The tests above can be repeated for 2 out of 3 and for 3 out of 3 operation mode.
6.4.1.2 Completing the test
Continue to test another function or end the testing by setting the parameter TestMode to
Disabled under Main menu/Tests/IED test mode/TESTMODE:1. If another function is
tested, then set the parameter Blocked to No under Main menu/Tests/Function test
modes/Voltage/UV2PTUV(27,2U<)/UV2PTUV:1 for the function, or for each
individual function in a chain, to be tested next. Remember to set the parameter Blocked to
Yes, for each individual function that has been tested.
Section 6 1MRK 505 293-UUS A
Testing functionality
76
Commissioning manual

Table of Contents

Other manuals for ABB REQ650

Related product manuals