ABB | SACE Emax 2
Ekip Touch - Settings
1 - Main settings
133 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Test Bus
The parameter allows parameter editing via the service connector to be enabled/disabled, thereby
limiting the possibility of configuring all the options on the display (in the Local mode) or via modules
Ekip Com
(in the Remote mode).
Disabling the parameter, Local mode and using the PIN allow security against undesired modification by
unauthorized persons to be increased.
NOTE:
with Test Bus= Off, communication via service connector is still guaranteed (reading
enabled)
Ekip Touch is supplied with the parameter set to: On.
System
The
System
menu provides various options:
Parameter Description Default
Date Setting the current date
Time Setting the current time
Language Setting the language in display menus English
PIN PIN setting (page#s#53) 00001
IMPORTANT: setting and checking Date and Time is important for all the recording
functions (trips or measurements); in the event of date and time glitches, reset and if
necessary replace the battery inside Ekip Touch (page 291).
View
The
View
menu provides various options:
Parameter Description Default
TFT orientation
Enables the orientation of the
Alarms List
,
Measuring Instruments
and
Main Measurements
pages to be set. The options are: Horizontal,
Vertical clockwise, Vertical counter-clockwise
Horizontal
Customer page
Allows you to activate a supplementary information page, which can
be accessed by pressing the iTEST button twice from any page with a
diagnosis bar. The information on the new page can be configured via
Ekip Connect (page#s#135)
Off
Ammeter
Phase
Allows the current to be displayed in the
Measuring instruments
page
to be set from among the following options: Imax, I1, I2, I3, Ne (only in
the 4P or 3P + N configuration)
Imax
Voltmeter
Phase
Allows the voltage to be displayed in the
Measuring instruments
page
to be set from among the following options: Vmax, V12, V23, V31
Vmax
Maintenance
The parameter allows an alarm, concerning maintenance of the unit, to be enabled/disabled. (page 116).
Ekip Touch is supplied with the parameter set to: On.