Ekip Touch - Settings
1 - Main settings
132 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Configuration
The
Circuit breaker-Configuration
menu, allowing the presence of the
External neutral
sensor to be
activated, is available for the 3P CB (page 258).
Activation of the configuration with
External neutral
(3P + N) enables:
histograms of phase Ne in the
Histograms
page
neutral current measurements
submenu for configuring the Neutral protection (
Neutral Protection
)
neutral current recording in the case of TRIP
With 3P CB, the parameter is set by default as: 3P.
Ground protection
In the earth
Circuit-breaker-Protections
menu of the LSIG version of Ekip Touch you can:
activate/deactivate the presence of external toroid S.G.R and relative Gext protection (page 257, 87).
activate the presence of Rc Toroid and relative protection (page 257, 90).
activate/deactivate the MDGF transformer presence and relative MDGF protection.
NOTE:
Rc Toroid can be activated if the Measuring Measurements package and Rc version
Rating plug are present; Toroid presence in the menu can only be deactivated afterwards
by replacing the installed Rating plug
With Ekip Touch LSIG, the parameter is set by default as: Absent.
Line frequency
Frequency adjustment is performed to set the installation frequency; the choice is between 50 Hz and
60 Hz.
NOTE:
the measurements are taken on the basis of the set grid frequency: incorrect
configuration of the parameter may lead to abnormal measurements and protection
Ekip Touch is supplied with the parameter setting that suits the ordered configuration.
Modules
The
Modules
menu provides various options:
Parameter Description Default
Local/Remote
The parameter defines the mode in which the parameters are written
in the unit:
Local
, parameter editing only via the display or service connector
Remote
, parameter editing only remotely (Ekip Com modules)
NOTES:
the Remote mode requires the presence of auxiliary power
supply and Ekip Com modules, otherwise it disables automatically
however, the Local/Remote parameter can still be edited in the
Remote mode
Local
Local bus
The parameter enables communication between the Trip unit and
modules installed via terminal box or outside the unit to be activated.
Correct communication between unit and modules is confirmed by:
• population of the
Modules
menu with all the modules connected
• Power Leds of the modules on and synchronized like the power led of
Ekip Touch
• absence of Local Bus alarm in the diagnosis bar
Off
Ekip Signalling
4K
Menu with the parameters of the Ekip Signalling 4K module, if present
Ekip Measuring Menu with the parameters of the module
Measurement
(page 205)
- Menu of every module connected and detected (from page 213)
Functions
Access to the
LOCAL Switch On
and
RESET signaling
functions (from
page 92)