ABB | SACE Emax 2
Internal electronic accessories
2 - Measurement
206 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Menu
The specific configuration area will activate in the
Settings
-
Modules
-
Ekip Measuring
menu if the
Measurement
module is detected correctly by Ekip Touch.
The following parameters can be configured in this menu:
Parameter Description Default
Voltage Transf.
Selects the presence or absence of the external transformer Absent
Un Setting Mode
Selects the rated voltage value selection mode:
• Table: value editable in preset steps
• Volt: value editable within the range in 1 V steps
Table
Rated voltage
Defines rated voltage Un.
Available in the absence of a transformer; defines rated
voltage Un.
The value is given in absolute value (Volts), editable within
the 100 V to 690 V range in steps which depend on the Un
Setting Mode parameter setting.
400 V
Primary voltage
Available in the presence of a transformer; defines rated
voltage Un of the installation.
The value is expressed in absolute value (volt) and can be set
within the 100 V to 1150 V range, in steps that depend on the
Un Setting Mode parameter setting.
400 V
Secondary voltage
Available in the presence of a transformer; defines the
secondary voltage of the transformer.
The value is expressed in absolute value (volt) and can be set
within the 100 V to 230 V range, in steps that depend on the
Un Setting Mode parameter setting.
100 V
Positive Power flow
Defines the power flow required for D protection; there are 2
options available (page#s#76):
• High Low: power flows from high terminals to low
terminals (load connected low)
• Low High, power flows from low terminals to high
terminals (load connected high).
Bottom
Top
Neutral connection
Available with 3P CB; allows the presence of the external
Neutral to be enabled.
NOTE:
presence of the neutral activates phase voltage
measurement
Absent
When Un Setting Mode is set according to Table the voltage parameters can have the following values:
Parameter Voltage values with adjustment in steps
Rated voltage
100 V, 115 V, 120 V, 190 V, 208 V, 220 V, 230 V, 240
V, 277 V, 347 V, 380 V, 400 V, 415 V, 440 V, 480 V,
500 V, 550 V, 600 V, 660 V, 690 V
Primary voltage
100 V, 115 V, 120 V, 190 V, 208 V, 220 V, 230 V, 240
V, 277 V, 347 V, 380 V, 400 V, 415 V, 440 V, 480 V,
500 V, 550 V, 600 V, 660 V, 690 V, 910 V, 950 V,
1000 V, 1150 V
Secondary voltage
100 V, 110 V, 115 V, 120 V, 200 V, 230 V