ABB | SACE Emax 2
External electronic accessories
7 - Ekip Com EtherNet/IP TM
230 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Connections
The module must be assembled in the first vacant slot of the terminal box after
Ekip Supply
, either on the
circuit-breaker (fixed version) or on the fixed part (withdrawable version).
For references about the connection and terminals, please consult document 1SDM000091r0001; a cable
of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication
bus.
To connect the module to Ekip Touch, please consult document 1SDH001000r0514.
Power supply
Ekip Com EtherNet/IP
TM
is supplied directly by the
Ekip Supply
module to which it is connected.
NOTE:
communication between Ekip Touch and the module is interrupted in the absence
of auxiliary power supply
Interface
the module has three signaling leds:
1
2
Figure 134
LED Description
Power
Signals the on status and correct communication with Ekip Touch:
• Off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module
on and communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes
per second): module on and communication with Trip unit absent
Link (1)
Indicates the communication state:
• Off: incorrect connection, signal absent
• on fixed: correct connection
Activity (2)
Indicates the communication state:
• off: no activity on the line
• flashing (activity on line present receiving and/or transmitting)
Configurations via menu
Local bus activation, which is essential for starting the communication between module and Ekip Touch,
is available in the
Settings
menu (page 49).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the
Settings
-
Modules
menu:
Parameter Description Default
Static IP address ON
Defines whether the module has the dynamic (Off) or
static (On) IP address.
Se = On all the associated parameters are enabled
OFF
Static address IP address
Enables the static IP to be selected 0.0.0.0
Static Network Mask
Enables the subnet mask to be selected 0.0.0.0
Static Gateway address
When there are several subnets, enables the IP address
of the node to which the module is connected to be
selected
0.0.0.0