External electronic accessories
7 - Ekip Com EtherNet/IP TM
231 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Information in menu
The following information will be available in the
About
-
Modules
menu if Ekip Touch has detected the
module correctly:
Information Description
SN and version
Identifier and SW version of the module
IP address
Address of the module, assigned to the module by a DHCP server at the time
of connection to the network in the case of configuration with a dynamic IP, or
can be set via the menu in the event of a static IP
NOTE:
without a DHCP server, the module automatically adopts a random
IP address within the 169.254.xxx.xxx
range
Network Mask
Subnet mask; identifies the method for recognizing the subnet to which the
modules belong and enables modules to be searched for within a defined set
of recipients.
Gateway address
IP address of the node to which the module is connected, in the presence of
several subnets
MAC address
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal
to ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
Remote configurations
Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Enable IEEE
1558
Allows the IEEE 1588 protocol for distribution of the clock and
synchronization signal to be enabled
(1)
.
OFF
IEEE 1558
Master
Enables the module to be set up as a master in the the network
segment to which it belongs (synchronization clock).
OFF
IEEE 1558 Delay
mechanism
Allows the data exchange mode between module and master,
either Peer-to-Peer or End-to-End, to be selected.
End-to-End
Enable client
SNTP
Allows the SNTP protocol for distribution of the clock and
synchronization signal to be enabled
(1)
OFF
ANTP Server
address
Allows the network server that supplies the SNTP to be set. 0.0.0.0
Time zone
Defines the time zone to be used for synchronism +00:00
Daylight Saving
Time
Used to select whether daylight saving time is present (ON) or
not (OFF) in the country to which the synchronization time refers
OFF
IEEE 1588
Boundary clock
Parameter useful if an IEEE 1588 GrandMaster clock is not
available:
• If enabled (ON), the module is seen as an IEEE1588 master
clock by all the slaves/devices in the same local network, even
when the source of external synchronism is different from IEEE
1588 (SNTP for example)
• If disabled (OFF) the module benefits from the synchronism of
the master in its own network
OFF
Enable
package
Limitation
Enables the Rate limiter function, which limits the number of
packages entering the module from the network, to be activated/
deactivated
Disable
(1)
Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
Remote information
Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
HW and Boot version
General module information
Flash CRC status and result
Information about the correctness of the SW in the module
Ekip Link status
Signals Ethernet cable connection errors
SNTP Server Error
Error in communication with SNTP server
SNTP Server Synchronization
State of synchronism with SNTP server
IEEE 1558 status
Valid with Master IEEE 1588= ON, notifies the presence (Slave
or PTP Master Active) or absence (PTP Master but Passive) of a
higher level master