1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 – XT4 | 154
From the service connector (via Ekip Connect) or with communication by system bus it is possible
to access additional parameters:
Preferred
configuration file
If several configuration files are present, it enables the file
hierarchy to be defined between .cid and .iid
Permits the IEEE 1588 protocol for distributing the clock and
synchronization signal to be enabled
(1)
Enables the module to be set as a master in the network
segment to which it belongs (synchronization clock)
IEEE 1588 Delay
mechanism
Enables the data exchange mode between module and
master, between Peer-to-Peer and End-to-End to be
chosen
Defines the time zone to be used for synchronism
Enables it to be selected whether there is daylight saving
time(ON) or not (OFF) in the country to which the
synchronization time refers.
Defines the file loading procedure:
TFTP always On= port open, loading still possible
TFTP enable required= port normally closed; to start
loading, the Enable TFTP command must be run at the
start of the procedure and the disable TFTP command
must be run at the end of the procedure (disable not
necessary, security command)
Defines the constraints for running remote open and close
commands:
standard commands = standard commands (without
constraints) active
CB operate request= standard commands not active;
use the programmable functions YC COMMAND and
YO COMMAND and the commands Request open
switch (28) and Request close switch (29)
set a filter on the selectivity status
NOTE: Enable IEEE 1558 and Enable SNTP client must not be enabled simultaneously