1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 – XT4 | 163
If the module is detected correctly by Ekip Touch in the About-Modules menu the following
information is available:
Identification and SW version of the module
Address of the module, assigned to the module by a DHCP server at
the moment of connection to the network in the event of configuration
with dynamic or settable IP that can be set by the menu in the event of
a static IP
NOTE: without a DHCP server, the module automatically
adopts a causal IP address in the interval 169.254.xxx.xxx
Subnet mask; identifies the method for recognizing the subnet to which
the modules belong and enables modules to be searched for within a
defined set of recipients
IP address of the node to which the module is connected, in the
presence of several subnets
Address assigned by ABB with OUI (Organizationally Unique Identifier)
equal to ac:d3:64 that identifies uniquely the manufacturer of an
Ethernet device
From the service connector (via Ekip Connect) or with communication by system bus it is possible
to access additional parameters:
Enables the CRL (Certificate Revocation List) to check the
validity of the server certificate
Clock update
hardening enable
Enables control of the time reference transmitted by the
SNTP server
Enables the position of the SNTP server to be set with
respect to the network in which the module is installed
Defines the time zone to be used for synchronism
SNTP Daylight
Saving Time
Enables it to be selected whether there is daylight saving
time(ON) or not (OFF) in the country to which the
synchronization time refers.
Permits (Enabled ARP) the periodic generation of a
Gratuituos ARP message to be enabled that is used by Ekip
Connect to find rapidly the modules with Ethernet scanning
without its IP address being known beforehand