1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 XT4 | 170
Connections
Consult
the electrical diagrams for 1SDM000068R0001 to connect the module to its
communication network and for terminal references.
For external cabling, AWG 22-16 cables with a maximum external diameter of 1.4 mm
must be used
the instruction sheets 1SDH002009A1503 to connect the module to Ekip Supply and
Ekip Touch
Supply
Ekip Com Synchrocheck is supplied directly by the Ekip Supply module to which it is connected .
NOTE: in the absence of an auxiliary supply, the communication between Ekip Touch
and module is interrupted
Input
Ekip Synchrocheck has an input (V S1 - V S2) for reading voltage, the operation of which is
ensured in the following ranges and with the following performance:
Component
Operating range
Normal operating interval
Accuracy
(5)
Voltage
0 .. 120 VAC
10 .. 120 VAC
1 %
(1)
Frequency
(2)
30 .. 80 Hz
30 .. 80 Hz
0.1 %
(3)
Phase
(4)
-
-180 ..+180 °
1 °
Isolation transformer
Between the external contacts of the switch and the input of the module, an isolation transformer
must always be installed that has the following characteristics:
Characteristics
Description
Mechanical
fixing: EN 50022 DIN43880 guide
material: self-extinguishing plastic
protection level: IP30
electrostatic protection: with screen to be earthed
Electrical
accuracy class: 0.2
performance 4 VA
overload: 20 % permanent
insulation: 4 kV between inputs and outputs, 4 kV between
screen and 4 kV outputs between screen and inputs.
frequency: 45-66 Hz