1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 XT4 | 171
Output
Ekip Synchrocheck has an output (K S1 - K S2) used as synchronism contact.
The output is insulated from the unit and the input and has the following electrical characteristics:
Characteristics
Maximum limit
(NOTE)
Maximum switchable voltage
150 VDC / 250 VAC.
Switching power
2 A @ 30 VDC, 0.8 A @ 50 VDC, 0.2 A
@ 150 VDC, 4A @ 250 VAC
Dielectric strength between open contacts
1000 VAC (1 minute @ 50 Hz)
Dielectric strength between each contact and coil
1000 VAC (1 minute @ 50 Hz)
NOTE: data on a resistive load
Interface
The module has two signalling LEDS:
Figure 44
LED
Description
Power
Reports ON status and correct communication with Ekip Touch:
off: module off
fixed or flashing light synchronized on power LED of Ekip Touch: module
ON and communication with Trip unit present
flashing not synchronized with power LED of Ekip Touch (two fast flashes
per second): module ON and communication with Trip unit absent
O SC
Indicate status of the contact of each output:
off: open contact
on: closed contact
NOTE: The LED shows output status: depending on the rest
configuration of the contact (normally open or closed), it can indicate
synchronization OK or Not OK