1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 XT4 | 174
Measurements
[2]
Measurement
Description
Auto detection
Busbar active = with automatic detection of the operating mode and operation
with busbar active, or with synchronism function not enabled
Dead busbar = with automatic detection of the operating mode and operation with
dead busbar
--- = Measurement not available (e.g.: because of manual detection of operating
mode)
Voltage
relation
VintVext = Internal voltage less than or the same as the external voltage
Vin>Vext = Internal voltage greater than the external voltage
--- = Measurement not available (e.g.: because of disabled synchronism or direct
voltage or less than 1 V)
frequency
relation
fintfext = Internal frequency less than or the same as the external frequency
fin>fext = internal frequency greater than the external frequency
--- = Measurement not available (e.g.: because of disabled synchronism, or
operation with dead busbar, or frequencies outside measurement range)
Summary Page
The summary page is activated in the presence of the module Ekip Synchrocheck; access is
possible as for the other summary pages (page 24).
In this page, the measures are:
V int: voltage read by Ekip Touch
f int: frequency read by Ekip Touch
Δᶲ: phase difference
SYNC: synchronization status
Information
In the About-Modules menu, the specific menu of the module is available, which contains the
serial number and the version of the module
Remote
information
From the service connector (via Ekip Connect) or with a system bus communication, additional
information is available on the version and the status of the module: HW and Boot version, CRC
status (correctness of SW in the module).