1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 – XT4 | 44
Function
The Neutral protection is used to differentiate the L, S and I protections on the Neutral phase,
introducing a different control factor with respect to the other phases.
The protection is available in 4P and 3P + N configurations. The configuration parameters are
accessible from the Settings - Circuit Breaker - Configuration menu (page 29).
Parameters
Activate/deactivate protection
Defines the multiplied factor applied to the tripping thresholds and
curves of the protections for the current read on Ne phase:
50 %: lower tripping thresholds for neutral current
100 %: same tripping thresholds for all phases.
150 %: higher tripping thresholds for neutral current.
200 %: higher tripping thresholds for neutral current.
NOTE: with 150 % / 200 % configurations and Ne current
is greater than 15.5 In protection is automatically adjusted
to 100%
Constraints, limitations, and additional functions
Ekip Touch rejects a change of the I1 and InN thresholds if the following constraint is not
respected:
(I1 x InN) Iu
- I1 is the threshold of the L protection in Amperes (ex.: In= 100 A and I1= 0,6 I1= 60 A)
- InN is the neutral threshold expressed as a multiplicative factor (example: InN= 200 %
InN= 2)
- Iu is the size of the CB
Allows activating an alarm in the event of distorted waveforms.
The protection can be enabled in the Measurements menu (page 28). If enabled an alarm is
activated for peak factors greater than 2.1.
IMPORTANT: the protection just manages the alert, not the trip
The T protection protects against abnormal temperatures detected by units.
It is always active and provides two states according to the temperature read:
-25 < t < -20 or 70 < t < 85
Display switched off; Warning LED ON @ 0.5 Hz
Display switched off; Alarm and Warning LED ON @ 2 Hz
The parameter Enable Trip can be enabled in the Settings - Circuit Breaker - T Protection menu
(page 29) to manage an opening command in the event of an alarm.
Hardware Trip, available in the Settings – Circuit Breaker – Hardware Trip menu (page 29),
protects against connection errors in Ekip Touch.
If enabled, if one or more of these events is detected:
Current sensors disconnected (phase or external if enabled)
Trip coil disconnected
Unit internal problems
an alarm is displayed and an opening command is sent.
IMPORTANT:
The protection is triggered if the error states persist for more than one second
In the event of an alarm due to Trip coil disconnection, only the signal is
managed