1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 XT4 | 75
Programmable
commands
Eight commands with programmable activation are available depending on signals or events.
Located in various Ekip Touch menus, the commands are:
Name
Description
Path (page)
External trip
Sends a TRIP command
Advanced -
Functions (27)
Trip RESET
Reset of the trip signal
Switch on SET B
Check protections set, from Set A to Set B
Energy RESET
Reset of energy counters
Measurements-
Energy (28)
YO Command
Sends an open command; it’s necessary the
presence of MOE-E
Settings - Functions
(29)
YC Command
Sends a close command; it’s necessary the
presence of MOE-E
Switch On LOCAL
Configuration change, from Remote to Local
Settings - Modules
-Functions (29)
Signalling RESET
Reset contacts of signalling modules
Parameters
Each command has two programmable parameters:
Parameter
Description
Default
Function
One or several events (up to eight, in AND or OR logic
configuration) to activate command.
The Custom configuration can be programmed via Ekip Connect
Deactivated
Delay
Is the minimum time of persistence of the event before the
command is sent; the value is expressed in seconds, which are
settable in a range: 0 s .. 100 s, with 0.1 s step