Commissioning
42/18-85-EN TZIDC-200, TZIDC-210, TZIDC-220 33
If Autoadjust is successful, the parameters will be stored automatically and the positioner will
revert to operating mode 1.1.
If an error occurs during Autoadjust, the process will be terminated with an error message. If
this happens, press and hold down or for approximately three seconds. The unit will switch
to the operating level, mode 1.3 (manual adjustment within the sensor range). The mount is
checked and corrected if necessary. Autoadjust then runs again.
6. Set potential dead band and tolerance band
This step is only required for critical (e.g., very small) actuators. It is not necessary under
normal circumstances.
1) The zero position is determined automatically and saved during Autoadjust (counter-clockwise (CTCLOCKW) for
linear actuators and clockwise (CLOCKW) for rotary actuators).