Ex relevant specifications
52 TZIDC-200, TZIDC-210, TZIDC-220 42/18-85-EN
Change from one to two column s
10.1.3 IECEx
10.1.3.1 Flameproof enclosure
Designation:
Ex d IIC T4/T5/T6
Type Examination Test
Certificate:
IECEx BVS 07.0030X, Issue No.: 0
Type:
TZIDC-200
Temperature class: T4, T5, T6
Electrical data
Voltage: 30 V AC/DC
A
mperage: 20 mA
Pneumatic data
Supply pressure: 6 bar
Thermal data
T4: -40 °C < T
amb
< 85 °C
T5: -40 °C < T
amb
< 80 °C
T6: -40 °C < T
amb
< 65 °C
Change from one to two column s
Special conditions for IECEx, flameproof enclosures
The positioner is designed for a maximum acceptable ambient temperature range
between -40 … 85 °C.
If the positioner is used at an ambient temperature above 60 °C or below -20 °C, use cable
entries and lines approved for a service temperature corresponding to the maximum ambient
temperature increased by 10 K or corresponding to the minimum ambient temperature,
respectively.
Variants that also meet the requirements for the "intrinsically safe" type of ignition protection
may not be used as "intrinsically safe", if they have been previously used as a flameproof
type of ignition protection.