Ex relevant specifications
42/18-85-EN TZIDC-200, TZIDC-210, TZIDC-220 63
10.3.3 IECEx
10.3.3.1 Flameproof enclosure
Designation: Ex d IIC T4/T5/T6
Type Examination Test
Certificate:
IECEx BVS 07.0030X, Issue No.: 0
Type:
TZIDC-220
Temperature class: T4, T5, T6
Permissible ambient
temperature:
T4: -40 °C < T
amb
< 85 °C
T5: -40 °C < T
amb
< 80 °C
T6: -40 °C < T
amb
< 65 °C
Standards:
IEC 60079-0: 2011
IEC 60079-1: 2007
Electrical data
Voltage: 30 V AC/DC
A
mperage: 20 mA
Pneumatic data
Supply pressure: 6 bar
Thermal data
T4: -40 °C < T
amb
< 85 °C
T5: -40 °C < T
amb
< 80 °C
T6: -40 °C < T
amb
< 65 °C
Change from one to two column s
Special conditions for IECEx, flameproof enclosures
The positioner is designed for a maximum acceptable ambient temperature range
between -40 … 85 °C.
If the positioner is used at an ambient temperature above 60 °C or below -20 °C, use cable
entries and lines approved for a service temperature corresponding to the maximum ambient
temperature increased by 10 K or corresponding to the minimum ambient temperature,
respectively.
Variants that also meet the requirements for the "intrinsically safe" type of ignition protection
may not be used as "intrinsically safe", if they have been previously used as a flameproof
type of ignition protection.