102
8. Product quality and environmental protection
The UniGear ZS1 type panels are produced in compliance with the requirements of international
standards for the quality management system and environmental management system. In these
fields, the excellent level is proved by quality certificates according to ISO 9001 and by the EMS
according to ISO 14 001.
End of life of product
The ABB company is committed to complying with the relevant legal and other requirements for
environment protection according to the ISO 14 001 standard.
The duty of company is to facilitate subsequent recycling or disposal at the end of product life.
During disposal of the product, it is always necessary to act in accordance with local legal requirements
in force.
We use the following methods of disposal:
Disposal can either be carried out thermally in an incineration plant or by storing on a waste site.
RAW MATERIAL RECOMMENDED METHOD OF DISPOSAL
Metal material (Fe, Cu, Al, Ag, Zn, W, others) Separation and recycling
Thermoplasts Recycling or disposal
Epoxy resin Separation of metal material and the disposal of rest
Rubber Disposal
Oil as dielectric (transformer oil) Draining from equipment and further recycling or disposal
SF
6
gas Discharging from equipment and further recycling or disposal
Packing material – wood Recycling or disposal
Packing material – foil Recycling or disposal

Table of Contents

Other manuals for ABB UniGear ZS1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB UniGear ZS1 and is the answer not in the manual?

ABB UniGear ZS1 Specifications

General IconGeneral
Rated Voltageup to 24 kV
Rated Currentup to 4000 A
Frequency50/60 Hz
Rated Short-Circuit Breaking Currentup to 50 kA
Rated Peak Withstand Currentup to 125 kA
InsulationAir-insulated
Type of SwitchgearMetal-clad
Rated Short-time Withstand Currentup to 50 kA for 3s
Internal Arc ClassificationIAC AFLR
Protection DegreeIP4X
Busbar SystemSingle and double busbar
Type Tested AssemblyIEC 62271-200
DimensionsVaries depending on configuration
WeightVaries depending on configuration