Unpacking
Remove the nails and crate lid and sides;
Open the compartment door and loosen the bolts fixing the switchgear to the pallet;
Lift the cubicles by means of the crane following the instructions below;
Remove the pallet;
Position the unloading shims;
Put the switchgear on the loading shims by using the crane.
Figure 30: Handling the switchgear in the wooden crate
Switchgear handling
Only use a suitable balanced lifting system.
Should an accidental fault cause a leakage of SF6, ventilate the room and carefully follow the
safety procedures prescribed in the IEC 1634 Standards.
After unpacking, lift the unit groups by means of a crane (figure 29). Use the eyebolts (1.5) and the ropes
fitted with safety.
After installation of the panels, remove the eyebolts used for lifting.
4.6.1.2 Handling by means of rollers
Only use rollers on a level floor.
Move the switchgear section avoiding any possible tilting.
Lift the switchgear section by means of a bridge or mobile crane or using jacks (figure 29); remove the
wooden pallet loosening the screws fixing it to the switchgear section base.
Put a sturdy metal sheet between the rollers and the unit base and place the switchgear on the sliding
rollers.

Table of Contents

Other manuals for ABB UniGear ZS1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB UniGear ZS1 and is the answer not in the manual?

ABB UniGear ZS1 Specifications

General IconGeneral
Rated Voltageup to 24 kV
Rated Currentup to 4000 A
Frequency50/60 Hz
Rated Short-Circuit Breaking Currentup to 50 kA
Rated Peak Withstand Currentup to 125 kA
InsulationAir-insulated
Type of SwitchgearMetal-clad
Rated Short-time Withstand Currentup to 50 kA for 3s
Internal Arc ClassificationIAC AFLR
Protection DegreeIP4X
Busbar SystemSingle and double busbar
Type Tested AssemblyIEC 62271-200
DimensionsVaries depending on configuration
WeightVaries depending on configuration