10029 29 28 3 4 Level SD/SD latch condition 1 = Level SD Latch is on
presently
10030
30
29
3
5
Low Gas SD/SD latch
condition
1 = Low Gas SD Latch is
on presently
10031 31 30 3 6 4-20mA Level Input (1)
Shutdown / SD Latch
1 = 4-20mA Level Input SD
has tripped and is active
10032
32
31
3
7 (MSB)
AUX2 Shutdown input
1 = AUX2 Shutdown input
is High (12VDC present,
shutdown sensor not
tripped)
10033
33
32
4
0 (LSB)
AUX1 Shutdown input
1 = AUX1 Shutdown input
is High (12VDC present,
shutdown sensor not
tripped)
10034 34 33 4 1 Low Gas Shutdown input 1 = Low Gas Shutdown
input is High (12VDC
present, shutdown sensor
not tripped)
10035
35
34
4
2
Unplug Detect signal
1 = Overlay is removed
(Alarm condition), 0 =
overlay is present
10036
36
35
4
3
Stop Button input
1 = Stop button is high, not
pressed, 0 = button is
pressed
10037
37
36
4
4
Start Button input
1 = Start button is high, not
pressed, 0 = button is
pressed
10038
38
37
4
5
CSC400 System State
1 = System On, 0 = System
Off
10039 39 38 4 6 Reserved Reserved
10040
40
39
4
7 (MSB)
4-20mA Pressure Input (2)
Shutdown / SD Latch
1 = 4-20mA Pressure Input
SD has tripped and is
active
10041
41
40
5
0 (LSB)
Igniter 2 Alarm input
1 = Alarm signal high
(Alarm indicated)
10042
42
41
5
1
Igniter 2 Valve input
1 = Valve signal high
10043
43
42
5
2
IGN2 Pilot Solenoid Fault
(Short)
1 = Solenoid fault (short), 0
= no fault
10044
44
43
5
3
IGN2 Main Solenoid Fault
(Short)
1 = Solenoid fault (short), 0
= no fault
10045
45
44
5
4
IGN2 TMain Solenoid Fault
(Short)
1 = Solenoid fault (short), 0
= no fault
10046
46
45
5
5
POC, IGN2 relay output
measurement
1 = POC relay output is
High (12VDC present),
IGN2
10047
47
46
5
6
Low Temp Alarm flag
1 = a Low Temp Alarm has
occurred
10048
48
47
5
7 (MSB)
Low Temp Shutdown flag
1 = a Low Temp Shutdown
has occurred