• The Push Button option allows the relay to be activated when the external push-button
contact is closed. This option is selected by default.
• The Locksaver (anti-tailgate) option truncates the relay timer when the door opens. This
ensures that the door will be locked as soon as it closes even if a very long relay time is
programmed. This also prevents overheating of the lock solenoid.
• The Chime option momentarily energizes the buzzer output whenever the door contact is
seen to open. The onboard buzzer also makes a chime sound.
• The Guest Button option activates the AUX relay for the programmed duration when the
key or key an externally connected keypad is pressed.
• The Exit Always option allows the holder of a valid enabled card to exit at all times
irrespective of the configured time zones.
• The Interlock option prevents the door being opened when the AUX input is active. OP3
activates when the door is open or the door relay is active.
• The Silent option prevents the door buzzer from sounding when access is granted or
denied.
• The Exit PIR option will keep the door open while the external push-button contact is
closed. This allows a PIR to be used as the exit switch.
• The Failsafe option sets the door relay to be normally energised. This means that the
door will open if the power supply to the controller fails.
• The Toggle Relay option allows the door to be toggled open or closed by users with the
Toggle Relay option enabled.
• The Exit PINs option configures the door to always require a valid PIN code before exiting
the door.
• Setting the Monitor Arming option indicates that the AUX input is connected to an
external alarm panel and is monitoring the alarm state. When the AUX input is low, the
panel is armed and access is denied to users. This option is only valid if the Arm Intruder
Alarm Option is also set.
• The Breakglass option indicates that the AUX input is connected to a breakglass unit.
• The Access Only option only activates the door relay on an access granted. Exit granted
will not activate the relay.
Alarms
This menu allows the installer to enable or disable a number of alarm events that can be
generated by the controller:
• The Door Forced alarm occurs when the door contact opens without the relay having
been energized. The AUX relay is activated until a valid card is presented.