44
42
Technical Specifications
Maximum Operating Pressure
Primary: 3 bar
Factory Test Pressure
Primary: 4.5 bar
Maximum Operating Temperature
90°C
Power Supply
230v 50Hz
Code 01130501 01130601 01130701
Fuel Oil (28 sec or 35 sec) or Natural gas/LPG
Burner options Riello oil - Riello pressure jet natural gas/LPG
Minimum input kW 22 30 40
Maximum input kW 28 41 57
Minimum output kW 20 28 36.5
Maximum output kW 25 36 51
Total capacity L 31 37 53
Primary connection (female BSP) Ø 1” 1” 1
1
/
4
”
Flue circuit pressure drop mbar 0.15 0.17 0.15
Flue connection (D) mm 130 130 150
Dimensions A mm 470 470 530
B mm 700 765 805
C mm 566 566 656
E mm 550 615 645
F mm 445 510 550
G mm 260 260 260
Weight empty (excluding burner) Kg 108 122 157
Weight full (excluding burner) Kg 139 159 210
Compact N1
Compact N2 Compact N3
Simple Installation
The Compact N is supplied fully assembled,with its
robust casing and insulation fitted in the factory.
This makes for a simple installation by the installer,
with heating flow and return and chimney
connections all easily accessible at the rear of the
boiler.There’s even a multi pin plug and socket for
electrical connection.