64
Display
symbol
Description Check point and suggestion
OPE1 Parameter lock CD00 set 1.
OPE2
FWD or REV
only
Motor direction limiter.
See function description CD18.
OPE3
Source of speed
command error
Set at analog command, but use F306 keypad
to change speed. Use CD19 to change
setting.
OPE4
Source of
operation
command error
Terminal control, F306 and RS485 can use
one only.
Use jumper to change setting.
OPE5 Over range error Operating error message ~ over range.
OPE6
Logic error
warning
Logic error when setting. (ex. CD05>CD04)
OPE7
Only changed in
standby
The parameter can only be changed in
standby mode.
OPE8
Read only
parameter
The parameter created by system. Unable to
be changed by user.
Mod Bus fail
Check all drives setting are accordance.
(address, communication speed, data format)
Check communication wires are A to A and B
to B.